Intelligent high-precision fault indicator independently developed by CYG ET: it integrates intelligent sensor technology, signal processing technology, artificial intelligence technology and information communication technology to realize access to energy at low power consumption, and relies on high-precision information acquisition and wide-range high-precision measurement to record waves, so as to realize accurate fault location of small current grounding system and retrospective inversion of complex fault process, thus effectively shortening the power outage time of line faults and improving the reliability of power supply. In addition, it has the functions of all-wireless power supply-free, rapid deployment based on live installation and dismantling and status monitoring perception, and supports the construction needs of ubiquitous IoT.
Intelligent High-Precision Fault Indicator
Overhead lines of 35kV and below for distribution network.
Product Overview
Product advantages
-
高精度信息采集,接地故障快速精准定位
高精度电流测量技术,使电流测量精度达到1%; 高精度的电场测量技术,解决电场误启动录波的问题,并且稳定性好,受环境影响极小; 三相同步测量技术,宽范围、高速度精准同步,保证接地故障快速精准定位 -
物联网全支撑,配电线路深度感知
物联网无线自组网技术,通过连接、扫码、组网三步,有效降低人工参与,带电安拆快速部署,提高安装效率。 与无线无源传感器技术等硬件新技术结合,实现配电线路状态全面感知,支撑配电线路状态检修与可视化抢修,提高运维效率 -
综合软硬件优化,一体化多元低功耗
通过低功耗MCU选型、双电容取电、系统架构优化设计及软件算法优化设计实现3A5S取能的全功能运行以及静态低于60μA的超低功耗 -
低功耗主控芯片
使用国产低功耗主控芯片,替代现有设备内国外芯片,实现设备主控芯片国产化替代需求,降低行业安全风险,同时支持国产芯片行业发展
Technical parameters
Item | JYL-SR | |
CPU | Acquisition unit | Cortex® M0 MCU, 16M |
Collection unit | Cortex® M0 MCU, 60M | |
Measurement and control function | Line current | 0~100A:±1A |
100~600A:±1% | ||
Electric field against earth | 0~4096:±1% | |
Battery voltage | 0~3.6V:±0.2% | |
Line temperature | 0~67℃:±1℃ | |
Protective alarm | Alarm mode | Recording+flashing light |
Anti-misoperation function | Load fluctuation + switching inrush current + line sudden connection + manual switching are not misoperated | |
Timing function | Timing mode | Support master station and GPS timing |
Recording synchronization | ≤30us | |
Power consumption control | Acquisition unit | ≤60uA |
Collection unit | ≤ 0.3VA (no communication online) | |
Protection level | Acquisition unit | IP67 |
Collection unit | IP55 |